Speak to the experts on 03456 445 002

Master Industrial

Power Range

30 - 80 kVA
  • 3:3

DC BUS 220 Vdc
Ideal for industrial installations

Master Industrial series UPS provide maximum protection and power quality for any type of load, especially industrial applications, such as manufacturing
and petrochemical processes, electrical distribution and power plants. Master Industrial is an on-line double conversion UPS (class VFI SS 111 in accordance with IEC EN 62040-3) with input and output isolation transformers.

Enquire About This Product

Downloads

Characteristics

Master Industrial is suited to the most demanding installation environments where there are vibrations, mechanical stresses, dust and in general where operating conditions are unfavourable to products created for the standard UPS market.

The high short-circuit current (ICC = 3) makes it suitable for loads that require high current peaks during switch-on or during normal operation.

The input and inverter transformers guarantee the isolation of the batteries, which are sized for a voltage of 220 Vdc (from 108 to 114 elements), the standard industrial value.

The input and inverter transformers guarantee the isolation of the batteries, which are sized for a voltage of 220 Vdc (from 108 to 114 elements), the standard industrial value.

Isolation transformer
Synchronisation device (UGS)
Hot connection device (PSJ)
Generator interface
Parallel configuration kit (Closed Loop)
Battery cabinets empty or for extended runtimes
Top Cable Entry cabinets
IP rating IP31/IP42

Technical Specifications

Rated power
30000 VA
Voltage 400 Vac three-phase
Voltage tolerance ± 20%
Frequency
50/60 Hz with autorange
Frequency tolerance 45/65 Hz
Power factor 0.93
Input current 145 A
Current distorsion <3% in 12MP HC version
Soft start 0-100% in 120" configurable
Rated voltage 400 Vac three-phase selectable 380 and 415
Voltage tolerance
± 15% (selectable from ± 10% to ± 25% from front panel)
Rated frequency
50/60 Hz (autorange)
Frequency tolerance Frequency tolerance
Rated current 145 A
Number phases 3
Back-feed protection yes
Overload capacity Inx10ms 14
Rated power 30000 VA
Active power 24000 W
Number phases 3 + N
Crest factor (Ipeak/Irms) 3 : 1
Waveform
Sinewave
Static stability ± 1%
Dynamic stability ± 5% in 5 ms
Frequency same as the input (autorange)
Voltage distortion with distorcing load <3%
Voltage distortion with linear load 1% (rated) 2% (max)
Frequency stability ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5% from front panel) with mains supply present
Inverter efficiency at rated load 95% %
Overload 125% 150% 200% of the rated current for 10^ / 1^ / 7§
Type Maintenance-free sealed lead-acid
Maximum recharge current
0.2xC10
Altitude max
1000 m
Color Light grey RAL 7035
Remote controls EPO and bypass
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Protection rating 3
Cooling (type) redundant fans
AC/AC efficiency 92,5%
Noise (at 1 m) 63 dBA at 1 m
Remote signals voltage free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm, output 12Vdc 80mA)
Operating temperature
0 ÷ 40 °C
Relative humidity 95% no condensing
Weight 850 kg
Dimensions (h w d) 1900x800x800 mm

Can't find what you're looking for?

Call us on 03456 445 002